BIPM is designed to insure intrinsic safety on a single (dual, BIPM-5K) AC/DC circuit. Barriers are typically used with different sensors driven in alarm and protection systems (in hazardous areas, classification 0,1,2, where flammable mixtures, of the categories IIA, group T1-T5 may be formed).

BIPM limit voltage and current in hazardous area circuits.

Technical specifications

Parameter BIPM-5/BIPM-5K BIPM-15/BIPM-15K BIPM-24/IBS-24K
Operating input voltage 5.5 VDC 16 VDC 26 VDC
Nominal input voltage 5 VDC 15 VDC 24 VDC
Max. input voltage (Um) 250 V
Max. output voltage (U0) 5.88 VDC 18.9 VDC 26.25 VDC
Max. output current (I0) 410 mADC 540 mADC 510 mADC
Max. capacitance (C0) 6.3 uF 6.3 uF 2.4 uF
Max. inductance (L0) 1 mH
Fuse nominal current 100 mA
Resistance 12.2 Ohm 28 Ohm 47 Ohm
Operating temperature range 0 to 45 °C
Explosion proof marking [Exia]IIA
Weight, max. 0.02 kg

Design

  • BIPM-5, BIPM-15, BIPM-24 designed in through hole mounted blocks (mounted on PCB);
  •  BIPM-5K, BIPM-15K, BIPM-24K designed in terminal blocks mounted on DIN rail.

Basic connections

Система Orphus