IEC Interface type Description Value Severity index/
Operation criteria

IEC 61000-4-28:1999

Electromagnetic Compatibility (EMC) – Part 4-28: Testing and Measurement
Techniques – Variation of Power Frequency, Immunity Test

Power port AC voltage pulse voltage 2 kV
5 kV
 
Analog/Digital input
Remote control outputs
I/O ports AC voltage
pulse voltage
0,5 kV
1 kV
IEC 60255-5:2000

Electrical relays – Part 5: Insulation coordination for measuring relays and protection
equipment – Requirements and tests
Digital inputs

Insulation tests (steady-state voltage)

2 kV AC А
Digital outputs
Remote control outputs
IEC 1000-4-8:1993 Framework port Long duration (60 s) 100 A/m 5/А
Short duration (3 s) 1000 A/m
IEC 1000-4-9:1993​ Framework port Long duration (60 s) 100 A/m 5/А
Short duration (3 s) 1000 A/m
IEC 1000-4-10:1993​ Framework port   100 A/m 5/А
IEC 61000-4-2:2008

Electromagnetic compatibility (EMC) – Part 4-2: Testing and measurement
techniques – Electrostatic discharge immunity test
Framework port Enclosure contact ± 6 kV 3/А
Enclosure air ± 8 kV
IEC 61000-4-3:2006

Electromagnetic compatibility (EMC) – Part 4-3: Testing and measurement
techniques – Radiated, radio-frequency, electromagnetic field immunity test
Framework port АМ 1kHz, 80 % 10 V/м
(80-1000) MHz
3/А

IEC 61000-4-4:2012

Electromagnetic compatibility (EMC) – Part 4-4: Testing and measurement
techniques– Electrical fast transient/burst immunity test

Power port Through coupling/decoupling device ± 2 kV
5 kHz
3/А
Analog/Digital inputs Through capacity clamp ± 2 kV
5 kHz
4/А
Remote control outputs ± 2 kV
5 kHz
4/А
I/O ports ± 1 kV
5 kHz
3/А
IEC 61000-4-5:1995

Electromagnetic Compatibility (EMC) – Part 4-5: Testing and Measurement
Techniques – Surge Immunity Test
Power port Line-to-line
Line-to-earth
± 1 kV
± 2 kV
2/А
3/А
Analog/Digital inputs Line-to-line
Line-to-earth
± 1 kV
± 2 kV
2/А
3/А
Remote control outputs Line-to-line
Line-to-earth
± 1 kV
± 2 kV
2/А
3/А
I/O ports Line-to-earth ± 0,5 kV 1/А
 
IEC 61000-4-6:1996

Electromagnetic Compatibility (EMC) – Part 4-6: Testing and Measurement
Techniques – Immunity to Conducted Disturbances, Induced by Radio-Frequency Fields
Power port Through coupling/decoupling device 10 V (0,15-80) MHz 3/А
Analog/Digital inputs
Remote control outputs Through immunity injection
clamp
I/O ports
IEC 61000-4-11:2004

Electromagnetic compatibility (EMC) – Part 4-11: Testing and measurement
techniques – Voltage dips, short interruptions and voltage variations immunity tests
Power port
(AC power supply)
Voltage interruption 0% Ur.
500 ms
X/А
Voltage dips 70% Ur.
1000 ms
Voltage dips 40% Ur.
500 ms
Voltage swells 120% Ur.
1000 ms
IEC 61000-4-12:2006
IEC 61000-4-18:2011


Electromagnetic Compatibility (EMC)
Part 4-12: Testing and Measurement Techniques - Oscillatory Waves Immunity

Part 4-18: Testing and measurement techniques – Damped oscillatory wave immunity test
Power port

Single damped oscillatory
transients
line-to-earth
line-to-line


Repetitive damped
oscillatory transients
line-to-earth
line-to-line

±  1 kV
±  2 kV
± 0,5 kV
± 1 kV

3/А
3/А


2/А
2/А

Analog/Digital inputs
Remote control outputs
IEC 61000-4-13:2002

Electromagnetic Compatibility (EMC) – Part 4-13: Testing and Measurement
Techniques – Harmonics and Interharmonics Including Mains Signalling at A.C. Power
Port, Low Frequency Immunity Tests
Power port
(AC power supply)
Combination of harmonic
components
less than 12% Ur. 3/А
IEC 61000-4-14:2009

Electromagnetic Compatibility (EMC) – Part 4-14: Testing and
Measurement Techniques – Voltage Fluctuation Immunity Test
Power port
(AC power supply)
  12% Ur. 3/А
IEC 61000-4-16:1998

Electromagnetic Compatibility (EMC) – Part 4-16: Testing and Measurement
Techniques – Test for Immunity to Conducted, Common Mode Disturbances
in the Frequency Range 0 Hz to 150 kHz
Power port 50 Hz (long duration)
50 Hz (short duration)
15 – 150 Hz
150 Hz – 1,5 kHz
1,5 – 15 kHz
15 – 150 kHz
30 V
100 V
30–3 V
3 V
3–30 V
30 V
4/А
4/А
4/А
4/А
4/А
4/А
Analog/Digital inputs
Remote control outputs
IEC 61000-4-17:1999

Electromagnetic Compatibility (EMC) – Part 4-17: Testing and Measurement
Techniques – Ripple on d.c. Input Power Port Immunity Test
Power port
(DC power supply)
  less than 15% Ur. 4/А
IEC 61000-4-28:1999

Electromagnetic Compatibility (EMC) – Part 4-28: Testing and Measurement
Techniques – Variation of Power Frequency, Immunity Test
Power port
(AC power supply)
  ± 15% fr. 4/А

 

Система Orphus