ARIS 4810/4820 is intended for data acquisition from intelligent electronic devices (IED) and other lower-level devices, for protocol conversion, data transfer to SCADA systems and control centers, interaction with other systems via standard protocols. It is used as an element of Smart Grid (FLISR), SAS.

Hardware platform

Intel Atom 1.91 GHz, RAM up to 4 GB DDR-3L, 8–64 GB SSD, 2BP, 4xLAN (10/100/1000 BASE-Tx), 2xEthernet 1000 Base-X, 10/100/1000 SGMII, 18xRS-485, 2xDI, 2xDO, 1xLIVE.

Main functions

  • Data acquisition from intelligent electronic devices (IED) and other lower-level devices
  • Broadcasting of remote control commands
  • Integration of devices of contiguous subsystems of relay protection, SIPS, fault localization, fault recording systems, etc.
  • Acquisition of oscillograms from microprocessor-based devices of relay protection, SIPS, fault localization, fault recording systems
  • Auxiliary calculation of parameters received from IED and other lower-level devices
  • Processing of custom algorithms, including online interlocking algorithms
  • Automatic linking with equipment of the lower and upper level systems
  • Multi-channel and multi-directional conversion of protocols of various devices and systems
  • Keeping an online archive with configurable data safekeeping period for cases of disconnection from upper-level data systems
  • Emission of data from the archive after the connection is restored
  • Keeping of a retrospective archive with a configurable depth
  • Emission of retrospective data upon request from top-level information systems
  • Processing of FLISR logic up to 1000 nodes monitored
  • Generation and transmission to upper level of diagnostic signals pertaining to status of communication links with lower-level devices
  • QNX 6.5 real-time operating system
  • Transmission of independent data sets in 10 directions to SCADA system and to upper levels

Basic performance data

  • Up to 10 000 tags processed per 1 second
  • Time synchronization via NTP, PPS, PTP
  • Support of PRP redundancy protocol
  • Not equipped with any fans or moving parts
  • QNX 6.5 real-time operating system
  • Transmission of independent data sets in 10 directions to SCADA system and to upper levels
  • RAID array for ARIS-4820 2x2.5 SSD version

Additional capabilities

  • Alarm signaling and self-diagnostics
  • Capability to operate as an NTP server
  • Built-in web-interface

Protocols for data reception from IEDs and other lower level devices

  • IEC 60870-5-101
  • IEC 60870-5-103
  • IEC 60870-5-104
  • IEC 61850-8-1 (MMS, GOOSE)
  • DLMS/COSEM
  • Modbus (RTU/ASCII/TCP)
  • GRANITE, TM-800A
  • SPA
  • START
  • OPC
  • SNMP
  • Proprietary protocols of manufacturers

Protocols for transmitting data to upper levels and contiguous systems

  • IEC 60870-5-101
  • IEC 60870-5-104
  • IEC 60870-6 (ICCP/TASE.2)
  • FTP/sFTP

Communication ports

  • 4xLAN (10/100/1000 BASE-Tx)
  • 2xEthernet 1000 Base-X, 10/100/1000 SGMII
  • 18xRS-485

Number of available modules per controller

2 slots for boards installation

Power supply

100–240 VAC (2 power supply units)

Overall dimensions

  • Frame size 2U
  • 440х90х315 mm (WxHxD)

Operating temperature range

–40...+65°C

Система Orphus