IEC

Interface type Description Value Severity index/Operation criteria

IEC 60255-5:2000

Electrical relays – Part 5: Insulation coordination for measuring relays and protection equipment – Requirements and tests

Power port

AC voltage
pulse voltage

2 kV 5 kV  

Analog/Digital inputs

Remote control outputs
I/O ports

AC voltage
pulse voltage

0,5 кВ 1 кВ

IEC 1000-4-8:1993

Framework port long duration (60s) 100 A/m 5/А
short duration (3s) 1000 A/m

IEC 1000-4-9:1993

Framework port long duration (60s) 100 A/m 5/А
short duration (3s) 1000 A/m

IEC 1000-4-10:1993

Framework port   100 A/m 5/А

IEC 61000-4-2:2008

Electromagnetic compatibility (EMC) –
Part 4-2: Testing and measurement techniques – Electrostatic discharge immunity test

Framework port

Enclosure contact ±8 kV 4/А
Enclosure air ±15 kV

IEC 61000-4-3:2010

Electromagnetic compatibility (EMC) –
Part 4-3: Testing and measurement
techniques – Radiated, radio-frequency,
electromagnetic field immunity test

Framework port АМ 1 kHz, 80%

10 V/м(80-1000) MHz

3/А

IEC 61000-4-4:2012

Electromagnetic compatibility (EMC) –
Part 4-4: Testing and measurement
techniques – Electrical fast
transient/burst immunity test

Power port Through coupling/
decoupling device

±4 kV
5 kHz

4/А
Analog/Digital inputs

Through capacity clamp

±4 kV
5 kHz
Х/А
Remote control outputs ±4 kV
5 kHz
Х/А
I/O ports ±2 kV
5 kHz
4/A

IEC 61000-4-5:1995

Electromagnetic Compatibility (EMC) –
Part 4-5: Testing and Measurement
Techniques – Surge Immunity test

Power port Line-to-line
Line-to-earth
±2 kV
±4 kV
3/А
4/А
Analog/Digital inputs Line-to-line
Line-to-earth

±2 kV
±4 kV

3/А
4/А

Remote control outputs Line-to-line
Line-to-earth

±2 kV
±4 kV

3/А
4/А

I/O ports Line-to-earth

±0,5 kV

1/A

IEC 61000-4-6:1996

Electromagnetic Compatibility (EMC) –
Part 4-6: Testing and Measurement
Techniques – Immunity to Conducted Disturbances, Induced by Radio-Frequency Fields

Power port Through coupling/
decoupling device
10 V
(0,15-80) MHz
3/А
Analog/Digital inputs Through immunity injection clamp
Remote control outputs
I/O ports

IEC 61000-4-29:2000

Electromagnetic Compatibility (EMC) –
Part 4-29: Testing and Measurement
Techniques - Voltage Dips, Short Interruptions and Voltage Variations on
d.c. Input Power Port Immunity Tests

Power port
(AC/DC power supply)

Voltage interruption

0% Ur.
500 ms

Х/А

Voltage dips 70% Ur.
1000 ms
Voltage dips 40% Ur.
500 ms
Voltage swells 120% Ur.
1000 ms

IEC 61000-4-12:2006

IEC 61000-4-18:2011

Electromagnetic Compatibility (EMC)
Part 4-12: Testing and Measurement
Techniques - Oscillatory Waves Immunity
Part 4-18: Testing and measurement
techniques – Damped oscillatory
wave immunity test

 

Power port

Single damped oscillatory transients
line-to-earth
line-to-line


Repetitive damped
oscillatory transients
line-to-earth
line-to-line

±2 kV
±4 kV

 

 


±1 kV
±2,5kV

4/А
4/А


3/А
3/А

Analog/Digital inputs

Remote control outputs

IEC 61000-4-13:2009

Electromagnetic compatibility (EMC) –
Part 4-13: Testing and measurement
techniques – Harmonics and interharmonics including mains signalling at a.c. power port, low frequency immunity tests

Power port
(AC power supply)

Combination of harmonic
components

up to 12% Ur.

3/А

IEC 61000-4-14:2009

Electromagnetic Compatibility (EMC) –
Part 4-14: Testing and Measurement
Techniques - Voltage Fluctuation Immunity test

Power port
(AC power supply)
  ±12 % Ur. 3/А

IEC 61000-4-16:1998

Electromagnetic Compatibility (EMC) –
Part 4-16: Testing and Measurement
Techniques - Test for Immunity to
Conducted, Common Mode Disturbances
in the Frequency Range 0 Hz to 150 kHz

Power port


50 Hz (long duration)



50 Hz (short duration)



15 – 150 Hz



150 Гц – 1,5 kHz



1,5 – 15 kHz



15 – 150 kHz

 

30 V



300 V



30– 3 V



3 V



3 – 30V


30 V

 

4/А



Х/А



4/А



4/А



4/А



4/А

Analog/Digital inputs

Remote control outputs

IEC 61000-4-17:1999

Electromagnetic Compatibility (EMC) –
Part 4-17: Testing and Measurement
Techniques - Ripple on d.c. Input
Power Port Immunity test

Power port
(DC power supply)

  Up to 15% Ur. 4/А

IEC 61000-4-28:1999

Electromagnetic Compatibility (EMC) –
Part 4-28: Testing and Measurement
Techniques - Variation of Power
Frequency, Immunity test

Power port
(AC power supply)
  ±15 % Ur. 4/А